3.
Design for Natural Ventilation
The design of controlled natural ventilation systems
requires identification of the prevailing wind direction, the strategic
orientations and positions of openings on the building envelope. These
openings include windows, doors, roof ventilators, skylights, vent shafts,
and so forth.
3.1 Ventilation rates
When designing a ventilation system, the ventilation
rates are required to determine the sizes of fans, openings, and air ducts.
The methods that can be used to determine the ventilation rates include:
(a) Maximum allowable concentration of contaminants
A decay equation can be used to describe the steady-state
conditions of contaminant concentrations and ventilation rate, like this:
| where |
Ci |
= maximum allowable concentration of contaminants |
|
|
Co |
= concentration of contaminants in outdoor air |
|
|
F |
= rate of generation of contaminants inside the
occupied space (l/s) |
|
|
Q |
= ventilation rate (l/s) |
|
(b) Heat generation
The ventilation rate required to remove heat from
an occupied space is given by:
 |
(4)
|
| where |
H |
= heat generation inside the space (W) |
|
| |
Q |
= ventilation rate (l/s) |
|
|
cp |
= specific heat capacity of air (J/kg.K) |
|
|
 |
= density of air (kg/m3) |
|
|
Ti |
= indoor air temperature (K) |
|
|
To |
= outdoor air temperature (K) |
|
(c) Air change rates
Most related professional institutes and authorities
have set up recommended ventilation rates, expressed in air change per
hour, for various situations. The ventilation rate is related to the air
change rate by the following equation:
 |
(5)
|
| where |
Q |
= ventilation rate (l/s) |
|
|
V |
= concentration of contaminants in outdoor air |
|
|
ACH |
= air change per hour |
|
Table 1 gives some recommended air change rates for
typical spaces. Table 2 provides some examples of outdoor air requirements
for ventilation.
Table 1 Recommended air change rates
|
Space
|
Air change rates per
hour
|
| Carparks |
6
|
| Kitchen |
20 - 60
|
| Lavatory |
15
|
| Bathrooms |
6
|
| Boiler rooms |
15 - 30
|
Table 2 Outdoor air requirements for ventilation
| Application |
Estimated maximum
occupancy (persons per 100 m2 floor area)
|
Outdoor air requirements
(l/s/person)
|
| Offices |
|
|
| - office space |
7
|
10
|
| - conference room |
50
|
10
|
| Retail's Stores |
|
|
| - street level |
30
|
5
|
| - upper floors/arcades |
20
|
5
|
| Education |
|
|
| - classroom |
50
|
8
|
| - auditorium |
150
|
8
|
| - library |
20
|
8
|
| Hospitals |
|
|
| - patient rooms |
10
|
13
|
| - operating rooms |
20
|
15
|
Note: Data source: ASHRAE Standard 62-1989,
Ventilation for Acceptable Indoor Air Quality.
3.2 Flow caused by wind
Major factors affecting ventilation wind forces include:
-
average wind speed;
-
prevailing wind direction;
-
seasonal and daily variation in wind speed and direction;
-
local obstructing objects, such as nearby buildings
and trees;
-
position and characteristics of openings through which
air flows; and
-
distribution of surface pressure coefficients for the
wind.
Natural ventilation systems are often designed for wind
speeds of half the average seasonal velocity because from climatic analysis
there are very few places where wind speed falls below half the average
velocity for many hours in a year.
The following equation shows the air flow rate through
ventilation inlet opening forced by wind:
 |
(6)
|
| where |
Q |
= air flow rate (m3/s) |
|
|
A |
= free area of inlet openings (m2) |
|
|
v |
= wind velocity (m/s) |
|
|
Cv |
= effectiveness of the openings (assumed to be 0.5
to 0.6 for perpendicular winds and 0.25 to 0.36 for diagonal winds) |
|
3.3 Flow caused by thermal forces
If the building's internal resistance is not significant,
the flow caused by stack effect may be estimated by:
 |
(7)
|
| where |
Q |
= air flow rate (m3/s) |
|
|
K |
= discharge coefficient for the opening (usually
assumed to be 0.65) |
|
|
A |
= free area of inlet openings (m2) |
|
|
h |
= height from lower opening (mid-point) to neutral
pressure level (m) |
|
|
Ti |
= indoor air temperature (K) |
|
|
To |
= outdoor air temperature (K) |
|
3.4 Guidelines for natural ventilation
The following guidelines are important for planning
and designing natural ventilation systems in buildings:
-
a natural ventilation system should be effective regardless
of wind direction and there must be adequate ventilation even when the
wind does not blow from the prevailing direction;
-
inlet and outlet openings should not be obstructed by
nearby objects;
-
windows should be located in opposing pressure zones
since this usually will increase ventilation rate;
-
a certain vertical distance should be kept between openings
for temperature to produce stack effect;
-
openings at the same level and near the ceiling should
be avoided since much of the air flow may bypass the occupied zone;
-
architectural elements like wingwalls, parapets and
overhangs may be used to promote air flow into the building;
-
topography, landscaping, and surrounding buildings should
be used to redirect airflow and give maximum exposure to breezes;
-
in hot, humid climates, air velocities should be maximised
in the occupied zones for bodily cooling;
-
to admit wind air flow, the long façade of the
building and the door and window openings should be oriented with respect
to the prevailing wind direction;
-
if possible, window openings should be accessible to
and operable by occupants;
-
vertical shafts and open staircases may be used to increase
and generate stack effect;
-
openings in the vicinity of the neutral pressure level
may be reduced since they are less effective for thermally induced ventilation;
-
if inlet and outlet openings are of nearly equal areas,
a balanced and greater ventilation can be obtained.
3.5 Barriers to the application of natural
ventilation
A successful application of natural ventilation strategies
is only possible when there are no problems in many areas at various levels
from the design stage to actual operating demands placed on the building
users (Allard, 1998). These potential barriers include:
-
Barriers during building operations
-
Safety concerns
-
Noise from outdoor
-
Dust and air pollution
-
Solar shading covering the openings
-
Draught prevention
-
Knowledge of the users about how to take the best advantage
of natural ventilation
-
Barriers during building design
-
Building and fire regulations
-
Need for acoustic protection
-
Difficult to predict pattern of use
-
Devices for shading, privacy & daylighting may hamper
the free flow of air
-
Problems with automatic controls in openings
-
lack of suitable, reliable design tools
-
Other barriers
-
Impact on architectural & envelope design
-
Fluctuation of the indoor conditions
-
Design a naturally ventilated building requires more
work but could reduce mechanical system (design fee on a fixed percentage
of system's cost)
-
Increase risk for designers
-
Lack of suitable standards
| Back
| Home | Next |
| Created: 17 Aug 2001
| Updated: 29 Apr 2003 | cmhui@hku.hk
|
|