A sub-main circuit can be defined as a circuit connected directly
from the main LV switchboard to a sub-main distribution panel or a rising
main for final connection of the minor current-using equipment. The Code
requires that the maximum copper loss in every sub-main circuit should
not exceed 1.5% of the total active power transmitted along the circuit
conductors at rated circuit current.
Similar approach could be followed for sizing conductor as feeder circuit
above. However, assumption has to be made in the design for various characteristics
of the sub-main circuit including design current, expected harmonic current
(THD) in the circuit, degree of unbalance, etc.
Alternatively, an energy efficiency method introduced by the Code could
also be used for preliminary cable sizing. This energy efficiency method
for cable sizing requires the calculation of the maximum allowable conductor
resistance based on the maximum copper loss requirement as stipulated in
the code.
For a 3-phase 4-wire circuit (assuming balanced, linear or non-linear):
Active power transmitted via the circuit conductors,
Total copper losses in conductors, Pcopper = (3 x Ib2
+ IN2) x r x L
where
UL = Line to line voltage, 380V
Ib = Design current of the
circuit in ampere
I1 = Fundamental current of the
circuit in ampere
IN = Neutral current of the
circuit in ampere
cos q = Displacement power factor of the
circuit
r = a.c. resistance / conductor
/ metre at the conductor operating temperature
L = Length of the cable in metre
Percentage copper loss with respect to the total active power transmitted,
% copper loss =
Therefore, max.
Table 4.2A and 4.2B
in the Code provide a quick initial assessment of cable size required for
the common cable types and installation methods used in Hong Kong.
The tabulated current rating of the selected cable could then be
corrected by applying the correction factors accordingly. The effective-current
carrying capacity of the selected cable must be checked so that its value
is larger than or equal to the nominal rating of the circuit protective
device.
A work example on sub-main cable sizing under different loading characteristics
is given below:
A 3-phase sub-main circuit having a design fundamental current of 100A
is to be wired with 4/C PVC/SWA/PVC cable on a dedicated cable tray. Assuming
an ambient temperature of 30oC and a circuit length of 40m,
calculate an appropriate cable size at the following conditions:
(a) Undistorted balanced condition using conventional method (cos q
=
0.85);
(b) Undistorted balanced condition with a maximum copper loss of 1.5%
(cos q
= 0.85);
(c) Distorted balanced condition with I3=33A & I5=20A
(THD 38.6%) and a maximum copper loss of 1.5% (cos q
=
0.85);
(d) Circuit lo feed VSD loads with harmonic current I5=70A,
I7=50A & I11=15A (THD 87%) and a maximum copper
loss of 1.5% (cos q
=1), and
(e) Circuit to feed 3 VSD loads as in (d).
Case ( a): Undistorted balanced condition using conventional
method:
Ib= 100A In= 100A
Assume the correction factors Ca, Cp, Cg
& Ci are all unity.

Refer to BS7671:1992, The Requirements for Electrical Installations.
Table 4D4A 25mm2 4/C PVC/SWA/PVC cable It
=110A
Conductor operating temperature tl = 30+ 1002/
1102 x (70-30) = 63oC
Ratio of conductor resistance at 63oC to 70oC
= (230+63)/(230+70)= 0.98
Voltage drop = 1.5mV/A/m x 0.98 x 100A x 40m=5.88V(1.55%)
Active power transferred
Total copper losses in conductors
=3 x 1002 A2 x 0.0015W/m
/
x 0.98 x 40m
= 1.02kW ( 1.82%)
Cable size of 25mm2 selected can comply with the safety
requirement but is not acceptable if the maximum allowable copper loss
is limited to 1.5%.
Case (b) Maximum copper loss method using
Table
4.2A in the Code for initial assessment of an approximate conductor
size required by calculating the maximum conductor resistance at 1.5% power
loss:
max. r (mW/m)
From Table 4.2A 35 mm2 4/C PVC/SWA/PVC
cable having a conductor resistance of 0.625 mW/m
is required.
Refer to BS7671:1992, The Requirements for Electrical Installations,
Table 4D4A 35mm2 4/C PVC/SWA/PVC cable
It=135A
Conductor operating temperature tl = 30 + 1002
/ 1352 x (70-30) = 52oC
Ratio of conductor resistance at 52oC to 70oC
= (230+52) / (230+70) = 0.94
Voltage drop= 1.1mV/A/m x 0.94 x 100A x 40m = 4.14V(1.09%)
Total copper losses in conductors = 3 x1002 x 0.625 x 094
x 40 = 716W(1.28%)
Cable size of 35mm2 selected is acceptable for both safety
and energy requirements, i.e power loss < 1.5%, under undistorted and
balanced conditions.
Case (c) Distorted balanced condition with I3=33A
& I5=20A (THD 38.6%) and a maximum copper loss of 1.5%
Fundamental current Il = 100A, harmonic currents I3=
33A & I5= 20A
Neutral current (rms) IN = 3 x 33A = 99A
Ler In = 125A
Fig. 4.1: Current Waveforms for case (c)
From case (b) above 35mm2 4/C PVC/SWA/PVC cable was selected
Refer to BS7671 1992. The Requirements for Electrical Installations,
Table 4D4A 35mm2 4/C PVC/SWA/PVC cable It=135A
Conductor operating temperature, tl = 30+ (3x107.2+99)2
/
(3x135)2 x (70-30)=73oC
(Note: conductor operating temperature would be 73oC at
this condition which is over the maximum of 70oC for PVC insulated
cable)
Ratio of conductor resistance at 73oC to 70oC
=(230+73)/(230+70) =1.01 (over temperature)
Total copper losses in conductors (assuming skin & proximity effects
are negligible for harmonic currents)
= (3 x 107.22 + 992) x 0.000625 x 1.01 x 40=
1.14kW
Active power,
% copper loss = 1.14kW / 56kW x 100 = 2% (over 1.5max.)
Try next cable size: 50mm2 4/C PVC/SWA/PVC cable
Refer to BS7671:1992, The Requirements for Electrical Installations,
Table 4D4A 50mm2 4/C PVC/SWA/PVC cable It=163A
Conductor operating temperature,
tl =30 +(3x107.2+99)2 / (3x163)2 x
(70-30) = 59.6oC
Ratio of conductor resistance at 59.6oC to 70oC
= (230+59.6) / (230+70) = 0.965
Total copper losses in conductors = (3 x 107.22 + 992)
x 0.000465 x 0.965 x 40 = 789W
% copper loss = 0.789kW / 56kW x 100 = 1.4%(<1.5%OK)
A cable size of 50mm2 is selected for compliance with both
safety and energy requirements under this condition.
Case (d):
Circuit to feed VSD loads with full load and full speed harmonic current
I5=70A, I7=50A & I11=15A (THD 87%)
and a maximum copper loss of 1.5% (cosq = 1)
Fig. 4.2: Current Waveforms for case (d)
Fundamental current, I1 = 100A
Harmonic current, I5=70A, I7=50A & I11=15A
New design current, Ib=Irms=133A
New rating of protective device, In=
160A
Minimum current-carrying capacity of conductors, It(min)
= 160A
Max. conductor resistance, r
From Table 4.2A 50mm2 4/C PVC/SWA/PVC
cable having a conductor resistance of 0.465 mW/m
is required.
Refer to BS7671 1992. The Requirements for Electrical Installations,
Table 4D4A 50mm2 4/C PVC/SWA/PVC cable It=
163A
Table 4D4B r = 0.8mV/A/m, x = 0.14mV/A/m,
z = 0.81 mV/A/m
Conductor operating temperature tl = 30+ 1332/1632
x (70-30) = 57oC
Ratio of conductor resistance at 57oC to 70oC
= (230+57) / (230+70) = 0.956
Voltage drop
Active power drawn
Total copper losses in conductors (assuming skin & proximity effects
are negligible)
= 3 x 1332 A2 x 0.000465 W/m
x 0.956 x 40m
= 0.94kW(1.4%)(<1.5% OK)
A cable size of 50mm2 is selected for compliance with both
safety and energy requirements under this condition.
Case (e) A riser is going to supply 3 nos. of VSDs as described
in Case (d) on 13/F, 14/F and 15/F of a building. No diversity factor is
to be applied.
Fundamental current, Il = 300A
5th harmonic current, I5 = 210A
7th harmonic current, I7 = 150A
11th harmonic current. I11 = 45A
Design current Ib = 398A
Rating of protective device, In = 400A
Min. cable current carrying capacity It(min) = 400A
Assume the floor-to-floor height is 3m and the cable is with a horizontal
run of 10m.
Actual cable length, L' = 10m + 15 x 3m = 55m
Effective cable length, L = 10m + 13 x 3m + 2/3 x 3m +1/3 x 3m = 52m
Max. conductor resistance

From Table 4.2A, 240mm2 4/C PVC/SWA/PVC
cable having a conductor resistance per unit length of 0.095 mW/m
is required.
Refer to BS7671:1992 The requirements For Electrical Installations.
Table 4D4A 240mm2 4/C PVC/SWA/PVC cable It =
445A
Table 4D4B r = 0.165 mV/A/m; x = 0.130 mV/A/m and z = 0.21 mV/A/m
Conductor operating temperature
Ratio of conductor resistance at 62oC to 70oC
Voltage drop
Active power drawn =
Total copper losses in conductors (assuming skin & proximity effects
are negligible)
= 3 x 3982A2 x 0.000095mV/A/m x 0.973 x 52m
= 2284W (1.16%<1.5%)
A cable size of 240 mm2 is selected for compliance with
both safety and energy efficiency requirements under this condition.